Dry-contact motion sensor NO vs NC: an integration checklist

Choosing between NO and NC on a dry-contact motion sensor starts with the receiving controller, not the terminal label alone. Among microwave motion sensors, a dry-contact model provides a change in contact state for a compatible control input. The installer must confirm how that input interprets an open or closed circuit, how long the sensor holds its motion state, and what happens when daylight prevents activation. A successful test follows the signal from movement through to the controller’s intended action.

Separate the sensor supply from the contact signal

A passive dry contact opens or closes an electrical path; it does not generate a powered output signal. This differs from an output that supplies a specified voltage when activated. Treating the two as interchangeable can produce an input that never changes state or an incompatible electrical connection.

Sensinova NOVA DC NONC needs its own 12-24 V DC supply to operate. That supply requirement is separate from its dry-contact output. Do not assume the contact supplies the sensor’s DC voltage to the receiving input, or that a controller’s sensing circuit can power the sensor. Confirm each circuit independently in the approved design.

Check the receiving input before selecting the contact

Read the receiver documentation for the exact input type, permitted electrical conditions and connection arrangement. Establish whether it accepts a passive contact, requires a powered signal, or uses a supervised circuit with additional components. Any required interface needs its own compatibility review. A contact rating alone is not permission to switch mains or LED loads, and this integration checklist is not a mains wiring procedure.

Define normal and motion states in plain language

For NOVA DC NONC, use the powered, settled no-motion condition as the commissioning reference. In that condition, COM-NC is closed and COM-NO is open. When motion activates the output, COM-NC opens and COM-NO closes. After the motion response and applicable HOLD period end, verify that the contacts return to their no-motion states.

Write the chosen pair and both states into the control schedule. For example, a design using COM-NO can specify an open contact in the settled no-motion condition and a closed contact during the active motion response. A design using COM-NC needs the opposite electrical interpretation. Neither choice automatically determines the receiver’s occupancy label or resulting action.

Keep loss of power outside this normal-versus-motion description. NO and NC labels do not establish the installed system’s behaviour during supply interruption, startup or recovery. Do not infer fail-safe operation, fault detection or a guaranteed power-failure contact state. Those conditions require documentation and a separate recorded test.

Match the electrical state to the controller logic

A closed circuit may appear as an active input, an inactive input or a configurable value in the receiving system. Read the input configuration and point definition rather than assuming that closed means occupied. Check whether the receiver responds to a maintained state or only to a change of state. A motion output held closed is not necessarily equivalent to the pulse expected by another input.

Confirm any inversion setting, filtering, controller delay and application override. Then agree the desired result for each state: the raw input value, the displayed occupancy status and the controlled action. A correctly changing contact with an incorrect software mapping can still leave the installation operating backwards.

The NOVA DC NONC dry-contact sensor combines indoor ceiling mounting and 5.8 GHz radar sensing with a passive contact interface. That interface does not establish universal BMS compatibility or provide a network protocol. Approval depends on the specific receiving input, its configuration and the demonstrated system response.

Include HOLD time and daylight in the test

Wait for the complete reset sequence

Record the selected HOLD setting before testing. Leaving the detection area does not mean the output should immediately return to normal. Observe the active period after the last movement and allow it to finish. Repeated movement during a check can affect the observed reset sequence, so record when movement occurs and verify the installed unit’s retrigger response rather than treating every extended activation as a fault.

Compare the contact transition with the receiver timestamp. If the contact has reset but the controlled action remains active, inspect the controller’s own delay, latch or override. Changing the sensor setting cannot resolve a downstream logic condition. Test with a repeatable movement pattern before choosing the final operating settings.

Distinguish daylight inhibition from an input fault

A daylight threshold can prevent a motion-triggered activation under brighter conditions. Record the threshold and ambient conditions for every trial. Establish a permitted test condition, then repeat under the intended daylight setting. Do not diagnose incompatible NO/NC logic solely because movement produces no activation in bright surroundings. Confirm the sensor’s permitted response first, then examine the receiving input.

Use an installer test matrix

Have a qualified installer follow the sensor and receiver instructions for inspection and measurement. Use an approved method that does not introduce an external voltage into an incompatible input. Record the actual contact state separately from the receiver’s raw value, displayed label and final action.

Test conditionContact checkReceiver and decision check
Powered, settled, no motionCOM-NC closed; COM-NO open.Confirm the selected pair produces the agreed no-motion value and action.
Motion with daylight permitting activationCOM-NC opens; COM-NO closes.Verify raw input change, correct occupancy mapping and intended action.
No further motion after activationObserve the HOLD period and return to normal.Separate sensor reset timing from receiver delays or latching.
Movement repeated during HOLDRecord the observed retrigger and reset sequence.Confirm the receiver handles the maintained state as intended.
Brighter conditions at the selected thresholdRecord whether activation is inhibited.Check that the application tolerates the resulting input state.
Approved supply interruption and recovery testMeasure actual states; do not assume them.Document receiver behaviour and whether the result meets the approved design.

Keep a usable commissioning record

Set acceptance criteria for the application as well as the input. If a controller displays occupancy, confirm what that label means when the sensor only reports a motion response. Include a trial with occupants remaining still if that matters to the intended control sequence. Do not treat a successful entry test as evidence of continuous presence detection. The project team should resolve any mismatch between the required occupancy behaviour and the selected sensing approach.

Retain the sensor model, supply verification, selected contact pair, daylight and HOLD settings, receiver model and input configuration. Include timestamps and results for each matrix row. If the contact behaves correctly but the application does not, assign the remaining issue to the receiving logic for investigation. Hand over unresolved conditions explicitly instead of marking the integration complete after a single successful walk test.

Frequently asked questions

Does a dry-contact motion sensor provide voltage to a controller?

The passive contact does not generate an output voltage. NOVA DC NONC still needs a separate 12-24 V DC supply. The receiver's documentation determines how its input senses contact opening and closing.

Should I use NO or NC for an occupancy input?

Choose the pair that matches the documented receiver logic and intended action. Test both no-motion and motion states. NC is not automatically a safety or fault-monitoring function.

Why does the controller still show motion after someone leaves?

The sensor may still be within its HOLD period, or the receiver may apply another delay or latch. Compare the measured contact reset with the raw input and application timestamps.

Can NO/NC labels predict what happens during a power failure?

No. Confirm the sensor and receiver documentation, then conduct an approved interruption and recovery test. Record actual contact states and controller actions rather than assuming an unpowered or restored condition.

Plan the interface before installation

For a sensor integration project, share the receiving controller’s input documentation, required no-motion and motion actions, and proposed commissioning conditions with Sensinova. Resolve contact compatibility and logic before finalising the design. Keep power interruption, daylight inhibition and reset timing in the acceptance test so the handover reflects the complete control sequence.

© Sensinova India 2026. All rights reserved.