How to Keep Office Lights On During Quiet Work

Sensinova true presence sensor for quiet office lighting

When a person sits at a desk reading, typing lightly or attending a call, a conventional motion sensor can let the lights time out. The fix is not always to extend the delay across an entire floor. Plan a detection zone around the actual seated positions, then test it with the lighting circuit and daylight conditions that occupants use.

Why a walk test alone misses the problem

A walk test proves that a sensor detects an entrance route. It does not prove that the same unit will keep the light on during a quiet meeting or focused desk work. Breathing-level detection helps with quiet work, but the seated area must still fall within the model’s smaller presence zone.

Compare the mounting options before marking the ceiling

NANO PRO-S is a ceiling-mounted surface option and NANO PRO-F is a flush-mount option. Both are specified for 5.8 GHz operation, 360-degree detection, 120-277 V AC supply, 400 W LED load, adjustable daylight threshold and a 5-second to 30-minute hold time. Their published breathing detection radius is 2-3 m, while movement and slight-motion radii are listed as 3-4 m. These are different zones: do not use the walk-detection figure to promise seated coverage.

DecisionNANO PRO-SNANO PRO-F
Installation formatSurface-mounted ceiling sensorFlush-mounted ceiling sensor
Published breathing radius2-3 m2-3 m
Published movement radius3-4 m3-4 m
Published LED load400 W400 W
Good reason to chooseSurface installation suits the ceiling planFlush appearance suits a prepared ceiling opening

Confirm the exact ceiling detail, wiring and compatibility with the lighting control design before ordering. Both models are marked IP20; do not specify them for wet or exposed locations without a suitable enclosure and an approved installation design.

Test a real seated occupancy pattern

1. Map chairs, desks and entrances separately

Place the intended seated positions on a plan. Compare their distance from the proposed ceiling point with the model’s stated breathing radius, then note glass partitions and nearby movement outside the room. A motion route and a quiet-occupancy zone are not interchangeable.

2. Check the output under daylight and quiet conditions

Have a qualified installer follow the product instructions and set a test delay and daylight condition suitable for commissioning. Walk into the zone, sit at the furthest intended chair and work quietly for longer than the test hold time. Repeat after adjusting placement or detection setting. Do not infer breathing detection from the light staying on after a recent walk-through.

3. Retest the adjacent space and restore operating settings

Test the corridor, neighboring room and moving equipment while the monitored room is empty. Tune the detection level and location to avoid unwanted switching, then restore the daylight threshold and hold time for normal use. If seated coverage and adjacent-zone separation cannot both be achieved, reconsider position or the number of zones.

A practical handover checklist

Record the exact model, ceiling height, zone drawing, load, daylight threshold, hold time and results for the furthest seated position and adjacent corridor. Sensinova lists a 2.5-4 m mounting-height range for these models; choose a position within the model instructions and verify performance on site. Electrical work belongs with a qualified installer.

Need help with seated-occupancy coverage?

Explore the true presence sensor range and send a seating plan to Sensinova before specifying the number and location of units.

Explore the models

FAQs

No. Detection depends on correct placement, settings and conditions. Test quiet occupants at the edge of the required zone, not just a walking entrance.
No. NANO PRO-S and PRO-F state a 2-3 m breathing radius and a 3-4 m movement radius. Plan the chairs against the smaller zone.
Both specify an LED load rating of 400 W. A qualified installer must still check the supply, drivers and full connected load.
The main published distinction is the installation format: PRO-S is surface-mounted and PRO-F is flush-mounted. Choose against the ceiling construction and access requirements.